COMBUSTION AIR & VENTING
WARNING:
Installationmethodsotherthanthosedescribed
inthefollowingsectionsmustcomplywiththe
NationalFuelGasCodeandallapplicablelocal
codesforprovidingsufcientcombustionair
tothefurnace.
Provisions must be made during the installation of this
unit that provide an adequate supply of air for combustion.
Instructions for determining the adequacy of an
installation can be found in the current revision of the
NFGC(ANSIZ223.1/NFPA54).Consult local codes
forspecialrequirements. These requirements are for
USinstallationsasfoundintheNFGC.
• TherequirementsinCanada(B149.1)arestructured
differently. Consult with B149.1 and local code officials
for Canadian installations.
WARNING:
Combustion air must not be drawn from a
contaminatedatmosphere.Excessiveexposure
tocontaminatedcombustionairwillresultin
safetyandperformancerelatedproblems.
To maximize heat exchanger life, the combustion air
must be free of chemicals that can form corrosive acidic
compounds in the combustion gases. The recommended
source of combustion air is to use clean air from outside.
DONOTplaceanychemicalswithammableorcaustic
vaporsortheseothercorrosivechemicalsnearthe
vent termination:
• Gasoline/Kerosene
• Permanentwavesolutions
• Chlorinatedwaxesandcleaners
• Chlorinebasedswimmingpoolchemicals
• Watersofteningchemicals
• De-icingsaltsorchemicals
• Carbontetrachloride
• Halogentyperefrigerants
• Cleaningsolvents
• Cements,glues,paintremovers,varnishes,etc.
• Hydrochloricacid
• Masonryacidwashingmaterials
• PlumbingStack
Air openings in the door of the unit, warm air registers, and
return air grilles must never be restricted. If the unit does
not receive an adequate supply of air for combustion, the
flame roll-out control located above the burners will open,
turning off the gas supply to the burners. This safety device
is a manually reset switch. IMPORTANT NOTE: DO NOT
installjumperwiresacrossthiscontroltodefeatits
functionorresetthecontrolwithoutidentifyingand
correctingthefaultcondition.
If this control must be replaced, use only factory authorized
replacement parts specified in the Replacement Parts
List provided online.
Vent Termination
This unit has been equipped with an integral venting
system and designed to operate only with this venting
system. If desired, an accessory venting kit is available.
UseonlyNORDYNEapprovedventingkitlistedinthe
technicalserviceliterature.
WARNING:
Thisunitisintendedforoutdoorinstallation
only.Donotventtheunitthroughaconventional
ventingsystem.
A vent cover assembly has been supplied with the unit
and can be found secured to the gas controls within the
burner area of this unit. Figure 1 displays the proper
installation of the vent cover assembly over the vent outlet
of the corner panel. The fasteners used to secure the vent
cover assembly have been included on the unit end panel.
The list below summarizes the location requirements for
theventingsystemtermination:
• Thelocationoftheventterminationmustbeconsistent
withtheNationalFuelGasCode(ANSIZ223.1)orCAN/
CGA-B149 Installation Codes.
• Mustbelocatedatleast4feethorizontallyfromany
electric meters, gas meters, regulators, and relief
equipment.
• Mustbelocatedatleast3feetaboveanyforcedairinlet
located within 10 feet of unit.
• Mustbelocatedatleast4feetbelow,4feethorizontally
from, or 1 foot above any door, window, or gravity air
inlet into any building.
• Mustbelocatedatleast1footabovegradeandinstalled
in such a manner as to prevent snow accumulation from
obstructing the vent termination.
• Theventterminationmustnotbelocatedaboveany
public walkways.
• Theventcoverassemblymustbeinstalledtoassure
proper operation of the unit.
Figure1.VentCoverAssembly