• Ifinstallingthisunitabove2,000feet,theinputratemust
bereduced4%per1,000feetofaltitude(Example:12%
at 3,000 feet, 16% at 4,000 feet, etc). Always round up
to the next highest value of 1,000. So an installation
at 3,120 feet is derated by 16% due to rounding up to
4,000. NOTE: This deration is necessary to compensate
for low atmospheric pressure at high altitudes. Generally
this will require obtaining the gas heating value from the
local gas utility and replacing the burner orifices.
• Table15(page40)liststhecorrectoricesizetouse
at different altitudes. To determine the unit rating and
orifice size, see the installation example.
• Afterchangingtheorices,itisrequiredthatyoumeasure
the gas input rate by clocking the gas meter and using
the local gas heating value. See section on Verifying
and Adjusting the Firing Rate on page 16.
IMPORTANT NOTE: Observe the action of the
burnerstomakesurethereisnoyellowing,lifting
orashbackoftheame.
Conversion to LP/Propane
WARNING:
The furnace was shipped from the factory
equippedtooperateonnaturalgas.Conversion
to LP/propane gas must be performed by
qualied service personnel using a factory
supplied conversion kit. Failure to use the
properconversionkitcancausere,explosion,
propertydamage,carbonmonoxidepoisoning,
personalinjury,ordeath.
INSTALLATION EXAMPLE:
Elevation: ..................................................3,890 feet
TypeofGas: .................................................. Natural
Unit Model: ................................... R6GP-090C200C
At 4,000 feet, the unit needs to be derated by 4% for
each 1,000 feet of elevation. This equates to 16% or
less than the sea level rating of 200,000 Btu/h.
1. Determineunitinputrating:
[200k x (100-16)%] = 168,000 Btuh. The required
heating rate for 3,890 feet is 168,000 Btu/h.
2. Determineoricesize:
FromTable15(page40),ndtheUnitModelNumber.
Follow across the row and stop at the 2,000-4,000
elevation column. For this example, the orifice size
displayed is #38. Install one #38 orifice in every burner
and check firing rate. In this example, the firing rate
must not exceed 168,000 Btu/h.
Figure9.TypicalGasServiceConnection
In the U.S., if installing the unit above 2,000 ft., refer
to Table 15 to determine the correct orifice size. When
conversion is complete, verify the input rate is correct as
listed in the tables. Approved conversion kit must be used.
Pleasefollowtheinstructionsprovidedwitheachkit.