7) Vent Terminal (Pipe
and Vent Cap)
The vent terminal pipe must be either Category III vent pipe or double-wall
(Type B). Terminate the vent pipe with a Reznor Option CC1 vent cap. A differ-
ent style vent cap could cause nuisance problems or unsafe conditions. The
vent cap must be the same diameter as the vent pipe.
See FIGURE 11 for requirements of a vertical vent terminal. See FIGURE 12
and the clearance table for requirements of a horizontal vent terminal.
FIGURE 12 -
Horizontal Vent
Terminal
(NOTE: Read all
measurements; drawing
is not proportional.)
Vent Pipe
(Comply with
Requirements
1) and 2) on
pages 16-17.)
Horizontal Vent Terminal Clearances
A vent cap is required. Maintain a minimum
clearance of 12 inches (305mm) from the wall
to the vent terminal cap for stability under wind
conditions.
Products of combustion can cause discoloration
of some building nishes and deterioration of
masonry materials. Applying a clear silicone
sealant that is normally used to protect concrete
driveways can protect masonry materials. If
discoloration is an esthetic problem, relocate the
vent or install a vertical vent.
Structure
Minimum Clearances for Vent Termination
Location (all directions unless specied)
Forced air inlet within 10 ft (3.1M) 3 ft (0.9M) above
Combustion air inlet of another
appliance
6 ft (1.8M)
Door, window, or gravity air inlet (any
building opening)
4 ft (1.2M) horizontally
4 ft (1.2M) below
1 ft (305mm) above
Electric meter, gas meter*, gas
regulator*, and relief equipment
U.S. - 4 ft (1.2M) horizontally
Canada - 6 ft (1.8M) horizontally)
Gas regulator * U.S. - 3 ft (0.9M); Canada - 6 ft (1.8M)
Adjoining building or parapet 6 ft (1.8M)
Adjacent public walkways 7 ft (2.1M) above
Grade (ground level) 1 ft (305mm) above**
*Do not terminate the vent directly above a gas meter or service regulator.
** Consider local snow depth conditions. The vent must be at least 6” (152mm)
higher than anticipated snow depth.
FIGURE 11 - Vertical
Vent Terminal
(
NOTE: Read all
measurements; drawing
is not proportional.)



























