Form I-LDAP, P/N 207733R6, Page 1
Applies to: Model LDAP, Indirect Fired,
Indoor, Downow,
Packaged Heaters
Installation/Operation/Maintenance
Reznor
®
Model LDAP 1200
Form I-LDAP (Version A)
(Obsoletes Form I-LDAP)

!
WARNING:
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in serious injury, death, or
property damage.
Be sure to read and understand the installation, operation, and service instructions in
this manual.
Improper installation, adjustment, alteration, service, or maintenance can cause
serious injury, death, or property damage.
Do not store or use gasoline or other ammable vapors and liquids in the vicinity
of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in your building.
Leave the building immediately.
Immediately call your gas supplier from a phone remote from the building. Follow
the gas suppliers instructions.
If you cannot reach your gas supplier, call the re department.
Installation and service must be performed by a qualied installer, service agency,
or the gas supplier.
Vista de pagina 0
1 2 3 4 5 6 ... 43 44

Indice de contenidos

Pagina 1 - WARNING:

Form I-LDAP, P/N 207733R6, Page 1Applies to: Model LDAP, Indirect Fired, Indoor, Downow, Packaged HeatersInstallation/Operation/Maintenance Reznor

Pagina 2 - 1.0 General

Form I-LDAP, P/N 207733R6, Page 10

Pagina 3 - Location

Form I-LDAP, P/N 207733R6, Page 11All piping must be in accordance with requirements outlined in the National Fuel Gas Code ANSI/Z223.1a (l

Pagina 4

Form I-LDAP, P/N 207733R6, Page 12

Pagina 5 - 

Form I-LDAP, P/N 207733R6, Page 13CAUTION: DO NOT bottom out the gas valve regulator adjusting screw. This can result in unregulated manifold pressure

Pagina 6 - 2.0 Heater Location (cont’d)

Form I-LDAP, P/N 207733R6, Page 14Adjust pressure by turning the regulator screw IN (clockwise) to increase pressure or OUT (counterclockwise) to decr

Pagina 7 - Dimensions

Form I-LDAP, P/N 207733R6, Page 15NOTE: Do not install louvers if installing a nozzle. Follow the instructions shipped with the nozzle.Louver Installa

Pagina 8 - Mounting the

Form I-LDAP, P/N 207733R6, Page 16

Pagina 9

Form I-LDAP, P/N 207733R6, Page 172) Vent Pipe Diameter and Length • Use only one diameter of vent pipe on an installation. • Minimum vent length is

Pagina 10 - 6.0 Mechanical

Form I-LDAP, P/N 207733R6, Page 18Support horizontal vent runs every six feet (1.8M). Support vertical runs of Type “B” double-wall or Category III ve

Pagina 11

Form I-LDAP, P/N 207733R6, Page 197) Vent Terminal (Pipe and Vent Cap)The vent terminal pipe must be either Category III vent pipe or doub

Pagina 12 - (cont’d)

Form I-LDAP, P/N 207733R6, Page 2WARNING: Gas-red appliances are not designed for use in hazardous atmospheres containing ammable vapors or c

Pagina 13

Form I-LDAP, P/N 207733R6, Page 20Check the rating plate on the heater for the supply voltage and current require-ments. A dedicated line voltage supp

Pagina 14

Form I-LDAP, P/N 207733R6, Page 21WD# 189504 REV. #3LDAP 400 - CL1, 22ROption CL1SINGLE STAGE THERMOSTATWGY2RW1GTWO STAGE THERMOSTAT Option CL22W2W1G

Pagina 15 - 

Form I-LDAP, P/N 207733R6, Page 227.2 24V Control Wiring (cont’d)7.0 Electrical and Wiring (cont’d)Multiple Heater Control - Option CL31 and Option CL

Pagina 16

Form I-LDAP, P/N 207733R6, Page 23Operating Sequence (all sizes)1. Set thermostat at lowest setting (fan switch at “AUTO” position).2. Turn on the m

Pagina 17 - 

Form I-LDAP, P/N 207733R6, Page 24FIGURE 17 – Typical Wiring Diagram for Model LDAP 400 (Reference W. D. 189374, Rev 3)Terminal Block - Heat Section #

Pagina 18

Form I-LDAP, P/N 207733R6, Page 25FIGURE 18 – Typical Wiring Diagram for Model LDAP 800 (Reference W.D. 189375, Rev 3)(Low Speed Destratification -fie

Pagina 19 - 

Form I-LDAP, P/N 207733R6, Page 26FIGURE 19 – Typical Wiring Diagram for Model LDAP 1200 (Reference W. D. 189376, Rev 3)(Low Speed Destratification -f

Pagina 20 - 7.0 Electrical and

Form I-LDAP, P/N 207733R6, Page 278.1 Combustion Air Proving [Pressure Switch(es)]8.2 Limit ControlEach heat section is equipped with a temperature ac

Pagina 21 - THERMOSTAT WIRING

Form I-LDAP, P/N 207733R6, Page 28Each heat section in this heater is equipped with a direct spark integrated control module (circuit board). The modu

Pagina 22 - LDAP 1200 THERMOSTAT WIRING

Form I-LDAP, P/N 207733R6, Page 29Normal Heat Cycle Operating Sequence1) Call for Heat - The thermostat calls for heat by energizing the “W” terminal.

Pagina 23 - 7.3 Fan Motor(s)

Form I-LDAP, P/N 207733R6, Page 3All Model LDAP high bay packaged heaters are design certied by ITS for use in industrial and commercial installation

Pagina 24 - Field Control Wiring

Form I-LDAP, P/N 207733R6, Page 30venter motor through post purge, and run the fan motor on heat speed for the selected delay off time.Abnormal Heat C

Pagina 25 - Destratification

Form I-LDAP, P/N 207733R6, Page 31Continuous Fan OperationLockoutsUndesired Flame - If ame is sensed longer than 20 seconds while the gas valve is de

Pagina 26

Form I-LDAP, P/N 207733R6, Page 329.0 Check Installation and StartupCheck to be sure that all screws used to hold shipping brackets were re-installe

Pagina 27 - Operation

Form I-LDAP, P/N 207733R6, Page 33FIGURE 21 - Gas Valve ON/OFF Control Knob9.3

Pagina 28

Form I-LDAP, P/N 207733R6, Page 34DANGER: The gas burner in this gas-red equipment is designed and equipped to provide safe controlled complete combu

Pagina 29

Form I-LDAP, P/N 207733R6, Page 35

Pagina 30

Form I-LDAP, P/N 207733R6, Page 36CAUTION: Use of eye protection is recommended.

Pagina 31

Form I-LDAP, P/N 207733R6, Page 37Ignitor - Refer to FIGURE 22 and locate the ignitor. Disconnect the wire; remove the screw and the ignitor. C

Pagina 32 - Installation

Form I-LDAP, P/N 207733R6, Page 38 Flame Sensor10.1.5 Heat Section Venter Motor and Wheel Remove dirt and grease from the motor casing, the venter hou

Pagina 33 - 9.3 Check

Form I-LDAP, P/N 207733R6, Page 3910.1.7 Fan Motor(s), Fan Blades, and Guard(s)FIGURE 28 - Fan Blade Position on the ShaftRemo

Pagina 34 - 10.0 Maintenance

Form I-LDAP, P/N 207733R6, Page 4Conned Space: A space whose volume is less than 50 cubic feet per 1000 BTUH of the installed appliance input rating

Pagina 35

Form I-LDAP, P/N 207733R6, Page 4010.1.9. Combustion Air Pressure Switch(es)See FIGURE 22, page 35, for location of the heat sec-tion pressure s

Pagina 36

Form I-LDAP, P/N 207733R6, Page 41The integrated circuit board monitors the operation of the heater and includes two LED signal lights that indicate n

Pagina 37 - 

Form I-LDAP, P/N 207733R6, Page 4210.2.1 General TroubleshootingPROBLEM PROBABLE CAUSE REMEDYVenter motor will not start 1. No power to unit. 1. Turn

Pagina 38

Form I-LDAP, P/N 207733R6, Page 43IndexAAbnormal Heat Cycle Functions 30BBurner Removal 35Burner Service 35CCheck installation after Startup 33Che

Pagina 39

Form I-LDAP, P/N 207733R6, Page 44www.RezSpec.com(800) 695-1901©2014 Reznor, LLC. All rights reserved. Trademark Note: Reznor® and TCORE2® are regis

Pagina 40

Form I-LDAP, P/N 207733R6, Page 5Hazards of Chlorine 2.3 Heater Throw NOTES: • X = Distance from “0” to beginning of oor coverage.• Y = Distance fr

Pagina 41 - 10.2 Troubleshooting

Form I-LDAP, P/N 207733R6, Page 63.0 Uncrating and PreparationIf the heater is being installed at an elevation above 2000 ft (610M), the input rate wi

Pagina 42

Form I-LDAP, P/N 207733R6, Page 7Instructions for Changing Heat section Pressure Switch(es)NOTE: Do not change the main pressure switch located on top

Pagina 43 - APPENDIX

Form I-LDAP, P/N 207733R6, Page 84.0 Clearances and Dimensions (cont’d)4.3 Dimensions - Models LDAP 800 and LDAP 1200FRONT VIEWBOTTOM VIEWRIGHT SIDE V

Pagina 44 - (800) 695-1901

Form I-LDAP, P/N 207733R6, Page 9WARNINGS: Check the supporting structure to be used to verify that it has sufcient load carrying capacity to support