Reznor RDF Unit Installation Manual Manual de usuario Pagina 10

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 28
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 9
I-RDF, PN148384R5, Page 10
Pilot Supply Pressure
These systems are designed to operate on a natural gas pilot supply pressure of 3.5"
w.c. or propane gas of 6.0" w.c. Measure both operating pressure and pilot supply
pressure with the blower in operation.
Manifold pressure is dened as the gas pressure as measured at the burner pressure
tap. Measure manifold gas pressure with the blowers operating. Minimum gas pres-
sure at the burner is typically 4.3" w.c. for natural gas or typically 1.5" w.c. for propane
gas.
FIGURE 8 - Pressure
Tap Locations for
Measuring Manifold
and Pilot Pressure
Manifold Pressure
Gas Pressure
Switches
High gas pressure switches included in the gas train monitor gas pressure downstream
from the safety valves. If the gas pressure at this point on a system equipped with a
high gas pressure switch (standard with Manifolds BM 78, 79, 80, and 81 or Option
BP2 with other manifolds) exceeds the setpoint, the switch will open the electrical
circuit to the burner, stopping all gas ow. The high gas pressure switch is a manual
reset device.
A low gas pressure switch (Option BP3) will shutoff the gas ow if the gas pressure
drops below the setpoint of the low pressure switch. The low gas pressure switch will
automatically reset when the gas pressure rises above the setpoint.
(NOTE: Model RDF units manufactured prior to April 1993 installed indoors with
optional gas pressure switches require a 3/4" vent line to the outdoors. Beginning with
units manufactured April 1993, the gas pressure switches incorporate a vent limiting
device and do not require venting to the outdoors.)
6.0 Mechanical
(cont'd)
Minimum Supply Gas Pressure ("w.c.) for Full Fire
Manifold Option BM75 BM76 BM77 BM78 BM79 BM80 BM81
with Gas Control
Option
AG1 AG3
AG 30, 31, 32, 33, 36, 37, 47, 48, or 51
Manifold Size 1" 1" 1" 1" 1" 1-1/4" 1-1/4" 2"
MBH Nat Pro Nat Pro Nat Pro Nat Pro Nat Pro Nat Pro Nat Pro Nat Pro
250 4.0 1.4 4.0 N/A 4.1 1.6 4.3 1.5 4.4 1.6 4.6 1.6 4.5 1.6 5.1 1.8
500 5.3 1.9 5.0 N/A 5.8 2.3 6.2 2.2 6.0 2.3 5.2 1.9 5.0 1.7 5.3 1.9
750 7.5 2.7 6.8 N/A 8.5 3.3 9.5 3.3 8.4 3.3 6.1 2.3 5.7 2.0 5.5 1.9
1000 12.4 4.7 11.7 4.6 7.4 2.8 6.7 2.4 5.8 2.1
1250 9.1 3.5 8.0 2.9 6.2 2.2
1500 11.2 4.3 9.6 3.5 6.6 2.4
1750 13.6 5.3 11.5 4.2 7.2 2.6
2000 16.5 6.3 13.7 5.0 7.8 2.8
2500 23.3 8.9 18.9 7.0 9.4 3.4
3000 11.3 4.1
6.1 Gas Piping and Pressures (cont'd)
Supply Pressure Requirement by Manifold Option (cont'd)










