14 SEER / 95% AFUE
SINGLE PACKAGE GAS HEATING / ELECTRIC COOLING
R8HE / PPG3HE SERIES
INSTALLATION INSTRUCTIONS
WARNING / AVERTISSEMENT
FIRE OR EXPLOSION HAZARD
•Failureto followsafety warnings exactly
couldresultinseriousinjuryorproperty
damage.
•Installationandservicemustbeperformed
byaqualiedinstaller,serviceagencyor
thegassupplier.
•Do not store or use gasoline or other
ammablevaporsandliquidsinthevicinity
ofthisoranyotherappliance.
WHAT TO DO IF YOU SMELL GAS
•Donottrytolightanyappliance.
•Donottouchanyelectricalswitch;donot
useanyphoneinyourbuilding.
•Leavethebuildingimmediately.
•Immediatelycallyourgassupplierfroma
neighborsphone.Followthegassuppliers
instructions.
•Ifyoucannotreachyourgassupplier,call
theredepartment.
RISQUE D’INCENDIE OU D’ EXPLOSION
•Lenon-respectdesavertissementsdesécurité
pourraitentraînerdesblessuresgraves,lamort
oudesdommagesmatériels.
•L’installationetl’entretiendoiventêtreeffectués
par un installateur qualié, un organisme de
serviceoulefournisseurdegazstaller,service
agencyorthegassupplier.
•Ne pas entreposer ni utiliser de l’essence ni
d’autresvapeursouliquidesinammablesdansle
voisinagedecetappareil,nidetoutautreappareil.
QUE FAIRE S’IL Y A UNE ODEUR DE GAZ
•Nepastenterd’allumeraucunappareil.
•Ne toucher à aucun interrupteur électrique;
n’utiliseraucuntéléphonedanslebâtiment.
•Évacuerl’immeubleimmédiatement.
•Appelerimmédiatementlefournisseurdegazen
employantletéléphoned’unvoisin.Respecterà
lalettrelesinstructionsdufournisseurdegaz.
•Sipersonnenerépond,appelerleservicedes
incendies.
DONOTDESTROY.PLEASEREADCAREFULLY&KEEPINASAFEPLACEFORFUTUREREFERENCE.
HORIZONTAL MOUNT SHOWN
3-PHASE&SINGLEPHASE(REVISIONA)
Vista de pagina 0
1 2 3 4 5 6 ... 51 52

Indice de contenidos

Pagina 1 - WARNING / AVERTISSEMENT

14 SEER / 95% AFUESINGLE PACKAGE GAS HEATING / ELECTRIC COOLINGR8HE / PPG3HE SERIESINSTALLATION INSTRUCTIONS WARNING / AVERTISSEMENTFIRE OR EXPLOSION

Pagina 2 - TABLE OF CONTENTS

10Figure4.RefrigerantServicePorts&Air ConditioningCondensateDrainLocationsHIGH SIDELOW SIDECONDENSATEDRAINSecuringScrewsFigure5.Interna

Pagina 3

11ELECTRICAL WIRING WARNING:ELECTRICALSHOCK,FIREOREXPLOSION HAZARDFailuretofollowsafetywarningsexactlycouldresultinseriousinjuryorprope

Pagina 4 - REQUIREMENTS&CODES

12• All208-240voltunitsareshippedfromthefactorywiredfor 240 volt transformer operation. For 208V operation, remove the lead from the transf

Pagina 5

13HeatAnticipatorVerify if the thermostat being used for the installation has a heat anticipator setting. This function allows the thermostat to anti

Pagina 6

14air-flow. Verify the selected rise is within the specification shown on the furnace rating label or in the tables.DehumidicationOptionsThe fixed spee

Pagina 7

15GASSUPPLY&PIPING WARNING:FIRE OR EXPLOSION HAZARD• Failuretofollowsafetywarningsexactlycouldresultinseriousinjuryorpropertydama

Pagina 8 - GroundLevel

16applied on each joint or union using a small paintbrush. If any bubbling is observed, the connection is not sealed adequately and must be retightene

Pagina 9

17Table3.ManifoldPressureSetting(inWC)forNaturalGasINPUT(BTUH)GASVALVESETTINGALTITUDE ABOVE SEA LEVELZERO TO 1,9992,00OTO2,999FT3,00OTO3

Pagina 10 - Securing

18STARTUP&ADJUSTMENTSPre-StartCheckList√ Verify the unit is level and allows evaporator condensate to drain.√ Verify heat exchanger condensa

Pagina 11 - AVERTISSEMENT:

191. Turn ON the manual gas valve, located on the outside of the unit to the ON position.2. Check all gas connections for leaks with a soap and water

Pagina 12 - % Voltage Imbalance

2TABLE OF CONTENTSIMPORTANT SAFETY INFORMATION... 3REQUIREMENTS&CODES...

Pagina 13 - Toavoidpersonalinjury

20unit data label. To determine the firing rate, follow the stepsbelow:1. Obtain the gas heating value (HHV) from the gas supplier.2. Shut off all oth

Pagina 14 - CAUTION:

213. Set the thermostat above room temperature and verify the units operating sequence (page 21). NOTE: The over-temperature limit control should turn

Pagina 15

22not close within 12 seconds, the control will display a Pressure Switch Open with Inducer On Fault. If the hall effect sensor switch does not close

Pagina 16

23BlockedVent/CondensateDisposalShutDownThe pressure switch is constantly monitored throughout the ignition cycle. After normal operation is est

Pagina 17

24local dealer about the availability of maintenance contracts. Routinemaintenanceshouldincludethefollowing: CAUTION:The unit should never be

Pagina 18

25CleaningofBurnersIf the burners must be cleaned, follow the steps below.1. Shut off the gas supply to the unit either at the meter or at a manual

Pagina 19

26FIGURES&TABLES2513.50161213.3116CGA3/4" NPTFEMALE DRAINCONNECTORBDOWNFLOWSUPPLY DUCTOPENINGDOWNFLOWRETURN DUCTOPENING23.5045.7513.501247.

Pagina 20 - Operation

27MODELNUMBERR8HE / PPG3HEUNITWEIGHTSHIPPINGWEIGHTCENTER OF GRAVITY UNITDIMENSIONS(INCHES)A BHEIGHT WITHBASE RAILSHEIGHT WITHOUTBASE RAILSLENGTH WID

Pagina 21

28AirowInformationTable8.CoolingAirowSettingsSWITCHSETTINGRECOMMENDEDAIRFLOW(CFM)SWITCHSETTINGRECOMMENDEDAIRFLOW(CFM)5 6 7 85 6 7 80 0 0 02TO

Pagina 22

29R8HE/PPG3HE-X24K060XA/-X30K060XA60,000BTUH,30”CABINET,11”X8”BLOWERW-3/4HPECMMOTOR230 VOLT OPERATIONSWITCHSETTINGS0.20 0.30 0.40 0.50

Pagina 23

3IMPORTANT SAFETY INFORMATIONPlease read all instructions before servicing this equipment. Pay attention to all safety warnings and any other special

Pagina 24

30R8HE/PPG3HE-X36*080(X,XA)80,000BTUH,30”CABINET,11”X8”BLOWERW-1HPECMMOTOR230 VOLT OPERATIONSWITCHSETTINGS0.20 0.30 0.40 0.50 0.60 0.70

Pagina 25

31Table12.BlowerPerformance-3.5TonR8HE/PPG3HE-X42K080XA80,000BTUH,34”CABINET,11”X10”BLOWERW-1HPECMMOTOR230 VOLT OPERATIONSWITCH SET

Pagina 26 - FIGURES&TABLES

32R8HE-X48*096(X,XA)&R8HE-X60*096(X,XA)96,000BTUH,38”-42”CABINET,11”X10”BLOWERW-1HPECMMOTOR230 VOLT OPERATIONSWITCH SETTINGS0.20 0

Pagina 27 - (DOWNFLOW APPLICATION)

33GasInformationTable14.GasPipeCapacitiesCAPACITYOFBLACKIRONGASPIPE(CU.FT.PERHOUR)FORNATURALGAS(SPECIFICGRAVITY-0.60)NOMINAL PIPED

Pagina 28 - AirowInformation

34Figure9.GasValveLabelA. This appliance does not have a pilot. It is equipped with an ignition device which automatically lights the burner. Do

Pagina 29

35Table16.ElectricalData.SINGLE PHASE MODELSMODELNUMBERR8HE / PPG3HEHEATINGINPUT(BTUH)INDUCERMOTORNOMINALELECTRICALSUPPLY VOLTAGERANGECOMPRESSORFAN

Pagina 30

36GREENREDSTATUSNOT USEDTEST PORTBLOWER MOTORRCY1TWINDEHUMW1EXPANSIONPORTCOOLHEATFAN SPEED1 2 345 6 78OFF ONFigure11.FixedSpeedMotorControlBoard

Pagina 31

37WIRING DIAGRAM208/230 Volt / 1 Phase / 60 Hz2-5 Ton Package 2 Stage Gas/Single Stage Air Conditioner NOTES:1. Couper le courant avant de faire letre

Pagina 32

38WIRING DIAGRAM208/230 Volt / 3 Phase / 60 Hz3-5 Ton Package 2 Stage Gas/Single Stage Air Conditioner NOTES:FIELD WIRINGLEGEND:LOW VOLTAGEHIGH VOLTAG

Pagina 33 - Input To Furnace (Btu/hr)

39WIRING DIAGRAM460 Volt / 3 Phase / 60 Hz3-5 Ton Package 2 Stage Gas/Single Stage Air Conditioner NOTES:1. Couper le courant avant de faire letretien

Pagina 34 - Figure9.GasValveLabel

4diagram before making any electrical connections to the unit. See the unit wiring label or Figure 13 (page 37), Figure 14 (page 38), & Figure 15

Pagina 35 - ElectricalData

40ChargingCharts26028030032034036038040042044046048050080 85 90 95 100 105 110 115 120Liquid Temperature (F)Liquid Pressure (psig)2 TON CHARGING CHAR

Pagina 36 - ElectricalDiagrams

4126028030032034036038040042044046048050080 85 90 95 100 105 110 115 120Liquid Temperature (F)Liquid Pressure (psig)3 TON CHARGING CHART60657075Add re

Pagina 37 - WIRING DIAGRAM

4228030032034036038040042044046048050080 85 90 95 100 105 110 115 120Liquid Temperature (F)Liquid Pressure (psig)4 TON CHARGING CHART520125130Remove r

Pagina 38

43APPENDIXA-HEATEXCHANGERCONDENSATEDRAIN&VENTKIT (HORIZONTALMOUNTAPPLICATIONS) WARNING:ELECTRICALSHOCK,FIREOR EXPLOSION HAZARDFailur

Pagina 39

44Preparing the pitAfter pit location has been determined, the condensate drain pit must be prepared for installation of the vertical 2” PVC vent pipe

Pagina 40 - 2.5 TON CHARGING CHART

45recommended for areas where temperatures are below 200 F for extended periods of time but is also dependent on the final depth of the trench if the f

Pagina 41 - 3 TON CHARGING CHART

46FROSTLINE 3" 2" - 3" ROCK BASEBELOW 2” PVC PIPE12" - 14"OR GREATER 4" - 6" OR DEEPER BACKFILLROCK/DIRTMIXTURERO

Pagina 42 - 5 TON CHARGING CHART

47APPENDIXB-HEATEXCHANGERCONDENSATEDRAIN&VENTKIT (ROOFCURBMOUNTAPPLICATIONS) WARNING:ELECTRICALSHOCK,FIREOR EXPLOSION HAZARDFailure

Pagina 43

48SettingtheUnitIMPORTANT NOTE:Beforehoistingandsettingtheunitinplace,theshortpieceoffactoryinstalleddrainlinelocatednexttotheun

Pagina 44 - READTHISBEFOREYOUDIG!

49ROOF MOUNTED UNIT(ROOF CURB AND ROOF NOT SHOWN)SpringHose Clamp2” PVC x 22.5 Degree Elbow& 1/4” Mesh Screen1/2” ID x 84”Drain HoseFlexible Insul

Pagina 45 - Preparing the Trench

5GENERAL INFORMATIONThis Single Package Gas Heating / Electric Cooling Unit is designed for outdoor rooftop or ground level slab installations and can

Pagina 48

Specifications & illustrations subject to change without notice or incurring obligations (07/14).709726A (Replaces 7097260)INSTALLATION / PERFORMAN

Pagina 49 - ROOF MOUNTED UNIT

6 WARNING:Combustible air must not be drawn from acontaminatedatmosphere.Excessiveexposureto contaminated combustion air will result

Pagina 50

7CIRCULATING AIR SUPPLY WARNING:Productsofcombustionmustnotbeallowedtoenterthereturnairductworkorthecirculatingairsupply.Failureto

Pagina 51

8ClearancestoCombustibleMaterialsThese units are certified as combination heating and cooling equipment for outdoor rooftop or ground level installa

Pagina 52 - ATTENTION INSTALLERS:

9• Securementofthedrainlinetotheinsidesurfaceofthe roof curb is acceptable and should be made in the wood nailer area (top 3.5”) to avoid p