INSTALLATION INSTRUCTIONS
EN ERGY RE COV ERY VEN TI LA TOR
Ap plies to Model XAWS
INSTALLATION INSTRUCTIONS FOR INDOOR STAND ALONE
ENERGY RECOVERY UNIT IN SIDE BY SIDE DESIGN
FORM RZ-NA-I-XAWS
MAY 29, 2014
SUPERCEDES 09-27-13
MXX-2ZERV
PAGE 1
I - Ship ping And Pack ing List
Package contains:
1 - Energy Recovery Ventilator Assembly
II - Ship ping Dam age
Check unit for shipping damage. Receiving party should
contact last carrier immediately if shipping damage is
found.
III - Gen eral
These instructions are intended as a general guide and do
not supersede local codes in any way. Authorities having
jurisdiction should be consulted before installation.
IV - Re quire ments
When installed, the unit must be electrically wired and
grounded in accordance with local codes or, in absence of
local codes, with the current National Electric Code,
ANSI/NFPA No. 70.
V - Ap pli ca tion
These Energy Recovery Ventilators (ERV) are used in a
horizontal discharge manner equipped with field
provided balancing damper assembly in the horizontal
duct work. A roof curb must be provided to Rooftop
Systems specifications. These wheels conserve energy by
mixing warmer air with cooler air in the following manner:
Re cov ery Wheel Mode
The Recovery Wheel mode is accomplished by two
blowers providing continuous exhaust of stale indoor air
and replacement by equal amount of outdoor air. Energy
recovery is achieved by slowly rotating the energy
recovery wheel within the cassette frame work. In winter,
the ERV adsorbs heat and moisture from the exhaust air
stream during one half of a complete rotation and gives
them back to the cold, drier intake air supply during the
other half rotation. In summer, the process is automatically
reversed. Heat and moisture are absorbed from incoming
fresh air supply and transferred to the exhaust air stream.
This process allows outdoor air ventilation rates to be
increased by factors of three or more without additional
energy penalty or increase in size of heating or air
conditioning systems.
VI - Rig ging Unit For Lift ing
1- Maximum weight of unit is — Varies per Series
{300-1200 Lbs.} (Crated)
2- Remove crating.
3- All panels must be in place for rigging.
VII - In stal la tion
1. Verify ERV is positioned and properly secured.
CAUTION
Danger of sharp metallic edges. Can cause injury.
Take care when servicing unit to avoid accidental
contact with sharp edges.
WARNING
Electric shock hazard. Can cause injury
or death. Before attempting to perform
any service or maintenance, turn the
electrical power to unit OFF at
disconnect switch(es). Unit may have
multiple power supplies.
2. Attach duct work to duct flanges on roof curb.
3. Remove ERV control access panel to connect field
wiring.
4. Route class II low voltage wire (3 conductor) from
thermostat or energy management through small
bushing in end panel of ERV. See wiring diagram.
a. Thermostat (dependent) - connect in parallel at
rooftop unit with "G", "C" and "W". Then connect
matching color at terminal 1, 2, and 3 respectively
on ERV circuit board.
b. Energy Management - provide +24 VAC to "1" and
common, 24 VAC to "2" terminals on ERV circuit
board.
c. Thermostat (dedicated) - splice into +24 vac (blue
wire) at (control circuit board) transformer
connection run wire to "R" terminal. Then run
another wire from "G" terminal to ERV (control
circuit board) terminal block #1.
5. All electrical connections must conform to any local
codes and current National Electric Codes (NEC) and
Canadian Electric Codes (CEC). Refer closely to unit
wiring diagram in unit and/or in these instructions for
proper wiring connections.
Energy recovery COMPONENT certified
to the AHRI Air-to-Air Energy Recovery
Ventilation Equipment Certification
Program in accordance with AHRI
Standard 1060-2000. Actual performance
in packaged equipment may vary.
ETL Certified per UL 1995
and CSA 22.2
Vista de pagina 0
1 2 3 4 5 6 ... 11 12

Indice de contenidos

Pagina 1 - Ap plies to Model XAWS

INSTALLATION INSTRUCTIONSEN ERGY RE COV ERY VEN TI LA TORAp plies to Model XAWSINSTALLATION INSTRUCTIONS FOR INDOOR STAND ALONEENERGY RECOVERY UNIT

Pagina 2

PAGE 10Mist Elimi na tor Fil ter in In take Hood (3HP)Ex ter nal Static Pres sure (in wa ter)0 0.25 0.5 0.75 1 1.25 1.5CFM2000 820 930 1015 1095 1160

Pagina 3

PAGE 11Mist Elimi na tor Fil ter in In take Hood (5HP)Ex ter nal Static Pres sure (in wa ter)0 0.25 0.5 0.75 1 1.25 1.5CFM4600 820 910 990 1020 1135 1

Pagina 4 - ERV Data Di men sional Data

START UP INFORMATION SHEET VOLT AGE - ERV UNITIn com ing Volt age L1-L2 L1-L3 L2-L3Run ning Volt age L1-L2 L 1-L3 L2-L3Sec ond ary Volt age C (bl

Pagina 5

6. Refer to the unit nameplate for minimum circuitampacity (MCA) and maximum overcurrent protectionsize (fuse).7. Electrical data is listed on unit ra

Pagina 6 - ERV UNIT WIR ING DIAGRAM

PAGE 3a - Disconnect power.b - Reverse any two field power leads to the ERV.c - Reapply power.5. Verify that both blower motors are operating underthe

Pagina 7

PAGE 4ABCStand Alone ERV’S For Side by Side In door ApplicationDDEIGHERV Data Di men sional DataSize CFM Range A B C D E F G H I11 300-1100 44.75 32.

Pagina 8

Notes:1. Re move jumper to in stall field op tional low am bi ent switch.2. Se lec tive volt age ter mi nal for proper unit volt age3. Op tional low

Pagina 9 - Blower RPM for XAWS11

PAGE 6Unit#: 01-M11-02XX-21Des ic cant Wheel for Roof top Unit208- 230V (1 PH)ERV UNIT WIR ING DIAGRAM :setoN.1 .hctiws tn ei bma wol lanoi tpo dleif

Pagina 10 - Blower RPM for XAWS28

PAGE 7Notes:1. Re move jumper to in stall field op tional low am bi ent switch.2. Step-down trans former as sem bly for 460/575 volt units.3. Se lec t

Pagina 11 - Blower RPM for XAWS46

PAGE 8Unit#: 01-M11-M62-02XX-23 thru -43Des ic cant Wheel for Roof top Unit208- 230/460/575V (3 PH)ERV UNIT WIR ING DIAGRAM :setoN.1 .hctiws tn ei bma

Pagina 12 - IN STAL LA TION CHECK LIST

PAGE 9Mist Elimi na tor Fil ter in In take Hood (2HP)Ex ter nal Static Pres sure (in wa ter)0 0.25 0.5 0.75 1 1.25 1.5CFM1200 1100 1225 1315 1405 1440