Form I-PDH-V, PN 211409R2, Page 2
2. Vent Pipe Diameter and Length
Use only one diameter of vent pipe on an installation.
Minimum vent length is 3 feet (1M).
TABLE 1 - Vent Pipe Diameter and Length for Horizontal or Vertical Vent
Vent pipe diameters and maximum vent lengths in TABLE 1 apply to either a horizontal
or a vertical vent. Add all straight sections and equivalent lengths for elbows. The total
combined length must not exceed the Maximum Vent Length.
Venting
Requirements
(cont’d)
3. Venter (Flue) Outlet
TABLE 2 - Venter
Outlet Size
Venter Outlet Attachment Requirements:
Depending on the size of vent pipe as determined in Requirement No. 2, attach either
the vent pipe directly to the collar or a taper-type connector (See TABLE 1).
FIGURE 1 - Venter
Outlet Location
Venter
Outlet
Sizes 75-150
16-13/16 (427mm)
Sizes 175-400A
17-1/4 (438mm)
Sizes 75-150
20-3/4 (527mm)
Sizes 175-400A
31 (787mm)
NOTE: Clearance from
vent connection must
be 18” (457mm).
Cabinet
Size
PDH
Vent Pipe
Diameter
Maximum Vent
Length
Equivalent
Straight Length
for 90° Elbow
Equivalent
Straight Length
for 45° Elbow
Field-supplied taper-
type connection
required at the venter
outlet
inches mm feet M feet M feet M
A
75 4 102 30 9.1 4 1.2 2 0.6 None
100 4 102 40 12.2 5 1.5 2.5 0.8 None
B
125 4 102 40 12.2 5 1.5 2.5 0.8 None
150 5 127 35 10.7 5 1.5 2.5 0.8 None
C
175 5 127 35 10.7 5 1.5 2.5 0.8 None
200 5 127 50 15.2 5 1.5 2.5 0.8 None
225 5 127 50 15.2 5 1.5 2.5 0.8 None
D
250 5 127 50 15.2 5 1.5 2.5 0.8
6” to 5” (152 to 127mm)
taper-type reducer
300 6 152 50 15.2 5 1.5 2.5 0.8 None
E
350
6 152 50 15.2 7 2.1 3.5 1.1 None
7 178 50 15.2 4.5 1.4 2.25 0.7
6” to 7”(152 to 178mm)
taper-type increaser
400A
6 152 50 15.2 8 2.4 4 1.2 None
7 178 50 15.2 5 1.5 2.5 0.8
6” to 7”(152 to 178mm)
taper-type increaser
Cabinet Size A B C D E
Model PDH 75 100 125 150 175 200 225 250 300 350 400A
Venter Outlet
Diameter
4 inches 5 inches 6 inches
102 mm 127 mm 152 mm
Side View